Type | Analog |
Brand | PIC |
Usage/Application | Power Relay |
Mounting Type | Wall Mounting Timer |
Automation Grade | Semi-Automatic |
Features*Switching the priming (oiling) pump after the set off time (12 hrs. & 24 hrs.)
*Continuously Independently adjustable 'On' time and 'Off' time.
*Instantaneous reset time.
*Digital circuitry for high accuracies.
*Immune to transients and surges.
*Life time guarantee of the unit (conditions apply)
DescriptionThis is a compact micro-electronic device made up of latest c-mos electronic components and other components of the highest quality available. This device is used to automatically switch ON and OFF the priming pump of the diesel generators periodically, in case of non-use of the generator. When the operating supply is connected to the device it starts counting the time and after the set OFF-time its relay gets energised for the set ON-time. This cycle of "OFF & ON TIME" continues till the operating supply is connected. Therefore to achieve the function of priming of generator, the operating supply of the device should be connected when the generator is OFF and the relay of the device should be used to put ON and OFF the priming pump.
Time RangeOff-Time :
Max. 12 Hrs. (Adjustable from 15 Mnt. onward) or
On-Time :
Max 5Mnts. (Adjustable from 30 sec. onward)
Setting/repeat Accuracy
± 2% of the time setting
Reset TimeReset time of the order of 100 m seconds normally and any variations can be provided against requirement.
Operating Voltage
*
12VDC or 24 VDC
*
110 VAC, 220VAC or 415 VAC 50 Hz.
Relay Contact Rating
*
2 Change over contacts rated for 6 Amp. resistive load or 2 amps inductive load
*
1 change over contact rated for 10 Amp. resistive load or 3.33 amps inductive load.
*
I.N.O. contact rated for 20 Amp. resistive load or 6.66 amps inductive load.
Insulation
The unit will withstand 2.5KV, 50Hz for one minute between all external A.C. supply and relay contacts terminals connected together and body.
Dimensions
Height 105, Base 51mm x 102mm
Burden
10VA (maximum)